Product Description

Portalevel Digital Liquid Level Indicator

The Portalevel Digital Liquid Level Indicator is the Ultimate Portable Co2 – Halon – FM-200® Liquid Level Indicator. As a professional fire engineer you will be conversant with the problems of servicing high pressure gaseous fire extinguisher systems. Using Portalevel™ brings immediate cost and safety benefits over traditional methods for verifying the contents of fire extinguisher systems, such as weighing and radioactive measurement.

  • For CO2 – Halon – Liquids (including FM200 replacements)
  • Identifies liquid levels in metal cylinders, pipework and single skinned holding vessels up to 25mm wall thickness
  • Accuracy levels +/- 1.5mm
  • Dry sensors requiring no gel or water
  • Special power boost for poor condition cylinders
  • Magnetic sensor for hands free application
  • No health and safety at work implications
  • No licensing, storage or IATA transportation restrictions

Specifications

Portalevel Digital Liquid Level Indicator – Specifications

Description Features
Function To indicate liquid gaseous extinguishants and other liquids in high or low pressure, single-skinned steel containers up to 89mm/3.5″ thick. Also functions on most types of single skinned industrial fluid containers including plastic
Type Portalevel ™ Digital
Liquids / Gases CO2, Halon, FM200 ™ , NAF S III, other Halon substitutes, LPG and other industrial liquids locatable
Sensor Ultrasonic single crystal sensor fitted with a magnetic head for hands-free operation. 16mm x 16mm
Accuracy ±1.5mm
Controls On / Off Switch, SPA (increases transmitter receive signal) switch, “CAL” self-calibration switch
Display Digital: LED and LCD digital display
Power Supply 4 x AA 1.5V Batteries. Consumption 230mA. Battery Life: 10 hours
Weight 500g
Dimensions Instrument: 155mm x 95mm x 45mm (Packed ex works for shipping incl carrying case: 34cm x 31cm x 18cm; Weight: 3.5Kg)
Operating Temperature Limited by the physical properties of the liquid gas. Optimum operating temperature
Ranges – CO2: 5 – 25°C, Halon and Halon replacements: 15 – 40°C
Calibration Portalevel Digital is self-calibrating.
Accessories “Wet” and “Dry” Sensors for poor condition and good condition cylinder surfaces respectively. Extension Rod with fixed 90 deg for 2-3-4 Multi-Banked cylinder row installations and pipe work

 

Data Sheet

Portalevel Digital Liquid Level Indicator – Data Sheet

Portalevel Digital Liquid Level Indicator Data Sheet

 

Accessories

Portalevel Digital Liquid Level Indicator – Accessories:

  • “Wet” and “Dry” Sensors for poor condition and good condition cylinder surfaces respectively.
  • Extension Rod with fixed 90 deg for 2-3-4 Multi-Banked cylinder row installations and pipe work

 

Instruction Manual

Portalevel Digital Liquid Level Indicator – Instruction Manual

Portalevel Digital Liquid Level Indicator Instruction Manual